Platform Maintenance
Platform maintenance
The
r5000/r10000/r12000 Series
platform contains components that you can replace individually without exchanging the entire system. This platform contains these replaceable components:- AC power supply
- DC power supply
- Fan tray (r5000-DF/r10000/r12000 Series only)
- Storage drive (r10000/r12000 Series only)
Power supply unit (PSU) replacement overview
F5 platforms support up to two AC
, DC,
or high-voltage DC (HVDC)
hot-swappable power supply units (PSUs). Some platforms come with only one PSU by default.
This platform includes two PSUs by
default.
Running without power supply units (PSUs) installed in
all available bays in the platform can affect cooling and electromagnetic
interference (EMI). If you need to run the unit with one PSU, you must install
a PSU blank into the empty PSU bay. The PSU blank is required to maintain
proper airflow in the system. If you do not have a PSU blank, leave all
supplies installed and disconnect power from any unused supplies.
Do not mix power supply unit (PSU) models of different
wattage. If two PSUs are installed in the same system, use only PSUs of the
same wattage and part number.
You
should use only one power supply unit (PSU) type (AC
, DC,
or HVDC) in a platform. AC/DC/
HVDC interoperability is not
supported.This product is sensitive to electrostatic discharge
(ESD). F5 recommends that you use proper ESD grounding procedures and
equipment when you install or maintain the unit.
Be sure to use only the power supply unit (PSU) that is
designed for your platform. For example, a lower wattage PSU might not
electrically connect if your platform is designed to use a higher wattage
PSU.
The power supply units (PSUs) do not have an on/off
switch. Power is controlled from the rack switch
or the mains power source
.After removing input power from any power supply unit
(PSU), wait 30 seconds before reapplying input power to the PSU.
AC power supply units (PSUs)
This platform can support up to two AC power supply units
(PSUs). You can hot swap a supply without powering down the system if there
are two installed, and one remains installed and operational during the
replacement process.
The platform supports PSU redundancy, which ensures that the
system is unaffected if a single supply fails in a system with more than one
operational supply installed.
When you add or replace a supply in your system, be sure to
verify the supply's features and that the PWR-XXXX part numbers match to
ensure that you have the correct supply.
On the 650W PSU, you can find the part number on
the top of the supply. For 650W AC, the part number is PWR-0306-xx, and for
650W DC, it is PWR-0307-xx. These supplies have a black vertical pull handle
and a silver-colored power cord face with rectangle-shaped perforations.
650W AC power supply unit (Part number:
PWR-0306-xx)

Example of label to check PWR-XXXX part
number

On the 1200W AC PSU, you can find the part
number (PWR-0388-xx) on the top of the supply. These supplies have a
cream-colored vertical pull handle and a black-colored power cord face with
rectangle-shaped perforations.
1200W AC power supply unit (Part number:
PWR-0388-xx)

Example of label to check PWR-XXXX part number

As a safety precaution, the socket
outlet must be installed near the equipment and be easily accessible.
You
should use only one power supply unit (PSU) type (AC
, DC,
or HVDC) in a platform. AC/DC/
HVDC interoperability is not
supported.Replace an AC power supply unit
In the event of a power supply unit (PSU)
failure, you can replace an AC PSU in your system. For a dual-supply system,
you can perform the replacement without powering down the system, provided
that there is at least one PSU operating during the replacement process.
Be sure that you are using the
correct wattage and part number (
PWR-0306-xx
PWR-0388-xx
) of power supply unit (PSU) in
all bays, as applicable, when performing a PSU replacement.All photos shown are examples. The appearance of your
power supply units (PSUs) might vary slightly, but be sure to use the pull
handle orientation and perforations in the power cord face to verify the
correct PSU for your platform.
- Prepare the system for PSU replacement:
- For a single-supply system, power off the system.
- For a dual-supply system, make sure that you have an operational supply already installed in your system if you want to hot swap a supply while the system is running. If you do not want to hot swap, you can perform the replacement with the system powered off.
- Before removing the PSU from your system, disconnect the AC power cord (input connector) from the PSU by pulling one or both of the power cord locking tabs away from the supply.Locking AC power cords might not be available in all countries.
- Remove the failed AC PSU by squeezing the ejector latch and pulling the handle straight toward you.After you remove a power supply unit (PSU) from the system, wait at least 30 seconds before you reinstall the PSU. Allow the PSU to fully discharge before you reinstall it.
- If an output connector protective cap is installed on your new PSU, remove it before installing the PSU into your system.
- Inspect the new PSU, especially the connector area and pins, for any damage that might have occurred during shipment.
- Slide the new PSU into the empty slot, and push it in until the ejector latch engages and clicks.While installing the supply, use care to ensure that the supply's connector does not come into contact with the rear of the chassis.
- Ensure that the PSU is fully seated in the chassis by making sure it does not come out when gently pulled.
- Insert the auto locking AC power cord into the PSU input connector and press firmly until it is fully seated.Be sure to route the power cords away from the fan tray so that the cords do not impede access to it.
- Connect the power cord to the power source.If the system is fully powered down and does not boot after you apply power to the PSU, use the touchscreen LCD to power on the system.
- Use the LCD touchscreen to clear any alert messages that might have resulted from performing the PSU replacement.
HVDC power supply units (PSUs)
This platform can support up to two high-voltage DC (HVDC) power
supply units (PSUs). You can hot swap PSUs without powering down the system if
there are two installed and one remains installed and operational during the
replacement process.
The platform supports power redundancy, which ensures that the
system is unaffected if a single supply fails in a system with more than one
operational supply installed.
On the 650W HVDC PSU, you can find the part number (PWR-0378-xx) on the top of the
supply.
650W HVDC power supply unit (Part number:
PWR-0378-xx)

On the 1200W HVDC PSU, you can find the part
number (PWR-0384-xx) on the top of the supply.
1200W HVDC power supply unit (Part number:
PWR-0384-xx)

Example of label to check PWR-XXXX part
number

You
should use only one power supply unit (PSU) type (AC
, DC,
or HVDC) in a platform. AC/DC/
HVDC interoperability is not
supported.The platform must be installed in a RESTRICTED ACCESS
LOCATION, such as a central office or customer premises environment.
After removing input power from any power supply unit
(PSU), wait 30 seconds before reapplying input power to the PSU.
Replace a high-voltage DC (HVDC)
power supply unit
You can upgrade your AC-powered
or standard DC-powered
system with
high-voltage DC (HVDC) power supply units (PSUs). In this case, you must
install two HVDC PSUs, even if your system previously included only one PSU.
You can also replace failed HVDC PSUs with replacement HVDC PSUs. For a dual-supply system, you can perform the
replacement without powering down the system, provided that there is at
least one PSU operating during the replacement process.
Be sure that you are using the
correct wattage and part number (PWR-0384-xx) of power supply unit (PSU)
in all bays, as applicable, when performing a PSU replacement.
All photos shown are examples. The appearance of your
power supply units (PSUs) might vary slightly, but be sure to use the pull
handle orientation and perforations in the power cord face to verify the
correct PSU for your platform.
- Prepare the system for PSU replacement:
- For a single-supply system, power off the system.
- For a dual-supply system, make sure that you have an operational supply already installed in your system if you want to hot swap a supply while the system is running. If you do not want to hot swap, you can perform the replacement with the system powered off.
- Be sure that the circuit breaker for the HVDC mains power source is switched off.
- Remove the failed HVDC PSU by squeezing the ejector latch and pulling straight toward you.After you remove a power supply unit (PSU) from the system, wait at least 30 seconds before you reinstall the PSU. Allow the PSU to fully discharge before you reinstall it.
- If an output connector protective cap is installed on your new PSU, remove it before installing the PSU into your system.
- Inspect the new PSU, especially the connector area and pins, for any damage that might have occurred during shipment.
- Slide the new PSU into the empty slot, and push it in until the ejector latch engages and clicks.While installing the supply, use care to ensure that the supply's connector does not come into contact with the rear of the chassis.
- Insert the auto locking HVDC power cord into the PSU input connector and press firmly until it is fully seated.Be sure to route the power cords away from the fan tray so that the cords do not impede access to it.
- Ensure that the PSU is fully seated in the chassis by making sure it does not come out when gently pulled.
- Connect the three ring terminals on the end of the cord to an approved power source.The -L wire connects to the negative terminal of an approved source, the +N wire connects to the positive terminal of an approved source, and the ground wire connects to Earth/Ground.
- Reapply input power from HVDC mains power source by switching the circuit breaker back on.If the system is fully powered down and does not boot after you apply power to the PSU, use the touchscreen LCD to power on the system.
- Use the LCD touchscreen to clear any alert messages that might have resulted from performing the PSU replacement.
DC power supply units (PSUs)
This platform can support up to two DC power supply units (PSUs). You
can hot swap PSUs without powering down the system if there are two
installed and one remains installed and operational during the replacement
process.
The platform supports power redundancy, which ensures that the
system is unaffected if a single supply fails in a system with more than one
operational supply installed.
On the 650W DC PSU, you can find the part number
(PWR-0307-xx) on the top of the supply.
650W DC power supply unit (Part number:
PWR-0307-xx)

On the 1200W DC PSU, you can find the part
number (PWR-0385-xx) on the top of the supply.
1200W DC power supply unit (Part number:
PWR-0385-xx)

Before installing a DC power supply unit (PSU), be sure
that the circuit breaker for the DC mains power to the PSU is switched
off.
Before you begin to work with one of
these platforms, refer to the DC-powered equipment environmental warnings for
this platform and review any safety requirements for the facilities where the
DC-powered platforms will be installed.
You
should use only one power supply unit (PSU) type (AC
, DC,
or HVDC) in a platform. AC/DC/
HVDC interoperability is not
supported.The platform must be installed in a RESTRICTED ACCESS
LOCATION, such as a central office or customer premises environment.
Copper cables used for grounding must meet
appropriate safety standards.
Bare conductors should be coated with an
appropriate antioxidant before being crimped. Make sure to clean all unplated
connectors, braided strap, and bus bars to a bright finish prior to coating
them with the antioxidant.
The platform must be grounded to a common
bonding network (CBN).
The battery return terminals on the
platform are in an isolated DC return (DC-I) configuration.
When you are running a redundant DC power supply
configuration, F5 strongly recommends that each DC power supply unit (PSU) in
the system receives power from independent DC main power sources with
independent circuit breakers.
After removing input power from any power supply unit
(PSU), wait 30 seconds before reapplying input power to the PSU.
Replace a standard DC power supply
Before you perform a DC power supply
unit (PSU) replacement, you need to provide these tools and components:
- 12 AWG copper cable long enough to reach from the platform to the DC power source
- Flat-head or Phillips head screwdriver
In the event of a power supply unit (PSU)
failure, you can replace a DC PSU in your system. For a dual-supply system,
you can perform the replacement without powering down the system, provided
that there is at least one PSU operating during the replacement process.
Be sure that you are using the
correct wattage and part number (PWR-0385-xx) of power supply unit (PSU)
in all bays, as applicable, when performing a PSU replacement.
All photos shown
are examples. The appearance of your power supply units (PSUs) might vary
slightly, but be sure to use the pull handle and power cord face perforations
colors to verify the correct PSU for your platform.
- Prepare the system for PSU replacement:
- For a single-supply system, power off the system.
- For a dual-supply system, make sure that you have an operational supply already installed in your system if you want to hot swap a supply while the system is running. If you do not want to hot swap, you can perform the replacement with the system powered off.
- Be sure that the circuit breaker for the DC mains power source is switched off.
- Remove the failed DC PSU by squeezing the ejector latch and pulling straight toward you.After you remove a power supply unit (PSU) from the system, wait at least 30 seconds before you reinstall the PSU. Allow the PSU to fully discharge before you reinstall it.
- If an output connector protective cap is installed on your new PSU, remove it before installing the PSU into your system.
- Inspect the new PSU, especially the connector area and pins, for any damage that might have occurred during shipment.
- Assemble the DC cable by connecting one of the included DC ring terminals to one end of each of your 12 AWG copper cables.
- Remove the terminal cover.
- Use a screwdriver to remove the screws from the DC power terminals.
- Connect the ring terminal for the positive (+) DC wire (typically red) to the left terminal, and the ring terminal for the negative (-) DC wire (typically black) to the right terminal.
- After you have attached the ring terminals to the terminals, secure them using a screwdriver.Use 13.5 inch-pounds (1.53 Newton-meters) of torque on these screws.
- If the chassis is not connected to Earth ground, connect the power supply Earth ground terminal to Earth ground.
- Verify that the DC power cables are connected to the appropriate terminal.The red wire should be connected to the terminal labeled positive (+), and the black wire should be connected to the terminal labeled negative (-).
- Replace the terminal cover.
- Slide the new PSU into the empty slot, and push it in until the ejector latch engages and clicks.While installing the supply, use care to ensure that the supply's connector does not come into contact with the rear of the chassis.
- Ensure that the PSU is fully seated in the chassis by making sure it does not come out when gently pulled.
- Reapply input power from DC mains power source by switching the circuit breaker back on.
- Use the LCD touchscreen to clear any alert messages that might have resulted from performing the PSU replacement.
Fan tray replacement overview
The fans in F5 platforms help maintain airflow
throughout the chassis and run constantly while the unit is powered on. Over
time, the fans can wear out, requiring you to replace the fan tray. For
platforms that have a removable fan tray, you can change or replace the fan
tray as part of the routine maintenance of the unit, or in the event of a fan
failure.
Fan tray

This product is sensitive to electrostatic discharge
(ESD). F5 recommends that you use proper ESD grounding procedures and
equipment when you install or maintain the unit.
Replace the fan tray
To ensure that you can easily access
the fan tray, route the power cords away from the fan tray so that the cords
do not drape over or cross in front of it.
You do not need special tools and
do not need to power down the unit when replacing the fan tray.
Operating the unit without a fan tray for more than 30
seconds might result in performance throttling or a thermal shutdown of the
unit.
- Locate the fan tray on the back of the chassis.
- Loosen the fan tray screws by turning them counterclockwise with a Phillips screwdriver.The screws that hold the fan tray in place are captive and cannot be removed from the assembly.
- Remove the fan tray from the chassis by grasping the handles and pulling straight toward you.
- Slide the new fan tray into the fan tray slot.
- Tighten the screws into place with a Phillips screwdriver.Use 5 inch-pounds (0.6 Newton-meters) of torque on these screws. The fan tray is connected to the system when you tighten the screws completely. Once seated, the fan tray automatically powers up and begins circulating air through the chassis.
Storage drive replacement overview
F5 r10000/r12000 Series platforms include two solid-state drives
(SSDs) that are configured with RAID enabled. In the event of a drive failure,
F5 sends you a new replacement drive for the faulty drive. For these platforms
you do not need to power down the system when replacing a drive as part of
routine maintenance or in the event of a drive failure.
Replacement drives provided by F5 do
not come pre-installed with software.
Storage drive location

When performing a storage drive replacement, you must remove
the failed drive from the software RAID array before physically removing the
drive from the
chassis.
Remove a faulty drive from the RAID array
Before you remove a faulty storage drive from
your system, you should identify the faulty drive and remove it from the RAID
array.
- Connect to the system using a management console or console server.The default baud rate and serial port configuration is 19200/8-N-1.
- Log in to the command line interface (CLI) of the system using an account with admin access.When you log in to the system, you are in user (operational) mode.
- Show the current status of the drives.show system raid raid-array-statusA summary similar to this example displays:appliance-1# show system raid raid-array-status ARRAY ARRAY NAME BAYID SERIAL NUMBER MEMBER STATUS SIZE ---------------------------------------------------------- ssd1 0 PHLJ912345PK1P0FGN true ok 684.7G ssd2 1 PHLJ912345Q61P0FGN true undefined 684.7GThe RAID array includes both storage drives as members. Note the serial number for the faulty drive and in which bay it is installed.
- Change to config mode.configThe CLI prompt changes to include(config).
- Remove the faulty drive from the RAID array.system raid remove drive ssd2A summary similar to this example displays:appliance-1(config)# system raid remove drive ssd2 status Remove of RAID SSD2 initiated. [11084.434517] md/raid1:md121: Disk failure on nvme1n1p3, disabling device. [11084.434517] md/raid1:md121: Operation continuing on 1 devices. [11084.449528] md/raid1:md122: Disk failure on nvme1n1p4, disabling device. [11084.449528] md/raid1:md122: Operation continuing on 1 devices. [11084.464098] md/raid1:md123: Disk failure on nvme1n1p5, disabling device. [11084.464098] md/raid1:md123: Operation continuing on 1 devices. [11084.478342] md/raid1:md124: Disk failure on nvme1n1p1, disabling device. [11084.478342] md/raid1:md124: Operation continuing on 1 devices. [11084.492509] md/raid1:md127: Disk failure on nvme1n1p2, disabling device. [11084.492509] md/raid1:md127: Operation continuing on 1 devices. status Remove of RAID SSD2 initiated.
Now you can physically remove the drive
and replace it with the new one that you received from F5. You do not have to
power down the system before you remove the drive.
Replace a storage drive tray in a dual-drive
system
To physically access the storage drives,
you must first remove the fan tray from the unit. Then you can remove the
faulty drive from the chassis and replace the faulty drive with a new one from
F5.
To access the storage drive in
this platform, you must remove the fan tray. Plan ahead to minimize the
amount of time that the unit operates without a fan tray. Operating the
unit at full load without a fan tray for more than 30 seconds might result
in performance throttling or a thermal shutdown of the
unit.
- Locate the fan tray on the back of the chassis.
- Loosen the fan tray screws by turning them counterclockwise with a Phillips screwdriver.The screws that hold the fan tray in place are captive and cannot be removed from the assembly.
- Remove the fan tray from the chassis by grasping the handles and pulling straight toward you.
- Verify the location of the faulty drive by identifying the drive bay that you noted earlier.
- Remove the faulty drive by pushing the blue lever in the middle of the drive tray to the left.The bottom drive tray contains SSD1, and the top drive tray contains SSD2.
- Pull the large latch straight toward you to eject the drive tray from the chassis.
- Slide the new drive tray into the empty drive bay until the latch engages the chassis.
- Push the latch inward toward the chassis until it clicks.
- Slide the fan tray back into the fan tray slot.
- Tighten the screws into place with a Phillips screwdriver.Use 5 inch-pounds (0.6 Newton-meters) of torque on these screws. The fan tray is connected to the system when you tighten the screws completely. Once seated, the fan tray automatically powers up and begins circulating air through the chassis.
Add a replacement drive to the RAID array
After you have physically replaced a faulty
drive with a new one from F5, you add the replacement drive to the software RAID
array.
- Connect to the system using a management console or console server.The default baud rate and serial port configuration is 19200/8-N-1.
- Log in to the command line interface (CLI) of the system using an account with admin access.When you log in to the system, you are in user (operational) mode.
- View the status of the drives.show system raid raid-array-statusA summary similar to this example displays:appliance-1# show system raid raid-array-status ARRAY ARRAY NAME BAYID SERIAL NUMBER MEMBER STATUS SIZE ---------------------------------------------------------- ssd1 0 PHLJ912345PK1P0FGN true ok 684.7G ssd2 1 PHLJ912345Q61P0FGN true undefined 684.7GThe status of the replacement drive isundefined, and the serial number should match that of the replacement drive.If after a few seconds, you do not see the replacement drive in the disk summary, the drive might not be seated properly. If this occurs, remove and reinsert the drive.
- Change to config mode.configThe CLI prompt changes to include(config).
- Add the replacement drive to the array.system raid add drive ssd2A summary similar to this example displays:appliance-1(config)# system raid add drive ssd2 status Add RAID SSD2 initiated.The array status for the new drive should change toreplicating, and the STAT LED should change to solid green. The replication process typically takes between 15 and 45 minutes.
- Return to user (operational) mode.end
- Verify that the new drive is added to the RAID array.show system raid raid-array-statusA summary similar to this example displays:appliance-1# show system raid raid-array-status ARRAY ARRAY NAME BAYID SERIAL NUMBER MEMBER STATUS SIZE ---------------------------------------------------------- ssd1 0 PHLJ912345PK1P0FGN true ok 684.7G ssd2 1 PHLJ967890Q61P0FGN true ok 684.7G
- Check if there are any active system alarms.show system alarmsIf there are any active alarms, they display in a summary similar to this example:appliance-1# show system alarms ID RESOURCE SEVERITY TEXT TIME CREATED -------------------------------------------------------------------------------------------- 66306 lcd ERROR Fault detected in LCD module 2021-11-11 10:11:28.602630317 UTC