Manual Chapter : Environmental Guidelines

Applies To:

Show Versions Show Versions
Manual Chapter

Environmental Guidelines

General environmental and installation guidelines

The VIPRION® 4800 platform is an industrial network appliance that is designed to be mounted in a standard 19-inch EIA rack. Follow these guidelines to adhere to safety precautions:

  • Install the rack according to the manufacturer's instructions and check the rack for stability before placing equipment in it.
  • Build and position the rack so that once you install the platform, the power supply and the vents on both the front and back of the unit remain unobstructed. The platform must have adequate ventilation around the unit at all times.
  • Although not required, a 1U space between units makes it easier for you to remove the unit from the rack in the event that the unit requires service. A 1U space between units also provides additional cable routing options.
  • Use an open-style rack or cabinet to reduce the restrictions to airflow. Use of a closed cabinet is not recommended. If a closed cabinet must be used, pay special attention to ensuring that there is adequate airflow on the front and rear of the chassis, as well as in and out of the cabinet.
  • The installation should be set up in a hot aisle-cold aisle configuration. Be sure to minimize leakage between the two sides.
  • Block off empty rack spaces to prevent back-to-front leakage of air flow. Recirculation of hot discharge air to the chassis air inlet will greatly impede the system cooling efficiency.
  • Ensure that your cabinet and data center arrangement has adequate air flow to minimize back pressure on the discharge side of the system. Restricting flow causes the chassis to run hotter than it needs to.
  • Use good cable dressing practices to help minimize detrimental effects on chassis cooling by reducing the amount of restriction to the chassis inlet. The VIPRION 4800 platform comes provided with cable managers. Avoid having cables hang in front of the chassis air inlet.
  • Do not allow the air temperature in the room to exceed 104°F (40°C).
    Note: NEBS-certified platforms can withstand air temperatures up to 131°F (55°C). The maximum temperature is only required to be met for a short period of time.
  • Do not plug the unit into a branch circuit shared by more electronic equipment than the circuit is designed to manage safely at one time.
Important: This product is sensitive to electrostatic discharge (ESD). F5 recommends that you use proper ESD grounding procedures and equipment when you install or maintain the unit.
CAUTION:
Customers should not attempt to replace batteries. There is a risk of explosion if a battery is replaced with an incorrect type. Field technicians should dispose of used batteries according to the instructions.
Attention: Il y a risque d'explosion si la batterie est remplacée par une batterie de type incorrect. Mettre au rebut les batteries usagées conformément aux instructions.

Earth guidelines

Service guidelines

Battery guidelines

Guidelines for the AC-powered platform

An AC-powered installation must meet these requirements:

  • Install the unit using a 20 amp external branch circuit protection device.
  • Normally, one power feed is used for each individual power supply.

The power requirements for the chassis are: 200-240 VAC ~, 50-60 Hz 16A Per Cord, Max 32 A total.

Important: The platform must be installed in a RESTRICTED ACCESS LOCATION, such as a central office or customer premises environment.
Note: The power cables included with this unit are for exclusive use with this unit and should not be used with other electrical appliances.
Note: These guidelines apply to STATIONARY PLUGGABLE EQUIPMENT TYPE A with simultaneous multiple connections to the AC MAINS SUPPLY:
  • The building installation shall provide a means for connection to protective earth; and
  • The equipment is to be connected to that means; and
  • A SERVICE PERSON shall check whether or not the socket-outlet from which the equipment is to be powered provides a connection to the building protective earth. If not, the SERVICE PERSON shall arrange for the installation of a PROTECTIVE EARTHING CONDUCTOR from the separate protective earthing terminal to the protective earth wire in the building.
Note: High leakage current. Earth connection essential before connecting supply.

Guidelines for the DC-powered platform

A VIPRION® DC-powered installation must meet these requirements:

  • Install the unit using a 100 amp external branch circuit protection device.
  • One power feed must be used for each individual power supply.
  • For permanently connected equipment, incorporate a readily accessible disconnect in the fixed wiring.
  • Use only copper conductors.
  • The DC MAINS powering the equipment shall be connected to protective earth.

The power requirements for the chassis are: 44-72 VDC, 62 A Per Cord, Max 124 A total.

Important: The platform must be installed in a RESTRICTED ACCESS LOCATION, such as a central office or customer premises environment.
Note: The power supply for the VIPRION® DC platform does not have an on/off switch. You control the power from the DC power source.
Note: You must use copper wire for the ground wire and all lead wires.
Note: You should coat bare conductors with an appropriate antioxidant compound before you make crimp connections. You should bring all unplated connectors, braided strap, and bus bars to a bright finish, and then coat them with an antioxidant before you connect them.
DC guidelines

NEBS platform guidelines

This information applies to the Network Equipment-Building System (NEBS) version of the VIPRION 4800 Series platform.

This equipment meets NEBS requirements per GR-63-CORE.

This equipment is suitable for installation in these locations:

  • Network Telecommunication Facilities
  • Locations where the National Electrical Code (NEC) applies
Important: The intra-building interfaces of this platform, including Ethernet, are suitable for connection to intra-building, or unexposed wiring or cabling only with shielded and grounded cables at both ends. The intra-building ports of the equipment must not be metallically connected to interfaces that connect to the outside plant (OSP) or its wiring.
Note: You should coat bare conductors with an appropriate antioxidant compound before you make crimp connections. You should bring all unplated connectors, braided strap, and bus bars to a bright finish and then coat them with an antioxidant before you connect them.

Chassis rack mount spatial requirements

The VIPRION® 4800 platform ships with a rack mount kit to help install the large system more easily. This kit requires that the rack or cabinet has certain clearances and spacing, as shown here:

Spatial requirements

Spatial requirements for rack mounting the VIPRION 4800 platform

Spatial requirements detailed view

Detailed view of spatial requirements for rack mounting the VIPRION 4800 platform

Platform power and airflow

The system installation needs to consider the power and air flow specifications of all installed equipment to ensure proper cooling. Although the maximum specifications for the VIPRION® 4800 chassis are listed here, the actual power and airflow vary depending on how the system is configured, the operating load, and the operating environment.

Max power ~5500W
Max airflow ~2200 cfm

Platform airflow diagram

When you install the platform into a rack, it is important to understand the unit’s airflow direction so that you can ensure proper cooling.

The platform employs a negative pressure fan system, which draws cold air in from the front of the chassis and exhausts hot air out the back of the chassis.

Platform airflow

Airflow in the VIPRION 4800 platform